- Cooling capacity at 95°F test condition
- 61,000 BTU/h
- Electrical supply
- 208–230 V / single phase / 60 Hz
- Current, manufacturer submittal primary table
- 32 A
- Fuse size
- 40 A
- LCDI plug configuration
- NEMA 6-50P
- Dimensions, width × depth × height, manufacturer submittal
- 29 × 51.5 × 60 in
- Net weight
- 661 lb
- Shipping weight
- 694 lb
- Evaporator airflow
- 1,700 CFM
- Condenser airflow
- 3,600 CFM
- Power cord length
- 6 ft
- Refrigerant
- R-410A
- Refrigerant charge
- 112 oz
- Cooling ambient temperature range
- 64–113°F
- Room-cooling area rating
- 1,700 sq ft
- Hot-air exhaust flange
- 20 in
- Controls
- Thermostatic control; self-diagnostic system; off timer
- Filters
- Washable
- Compressor protection
- Overload protection and restart delay
- Freeze protection
- Anti-freezing thermistor
- Power recovery
- Automatic restart
- Air delivery
- 3 directional nozzles
- Condensate management
- Built-in pump with overflow protection
- Maximum exhaust duct length, optional duct accessories
- 100 ft
- Maximum condenser air supply duct length, optional duct accessories
- 60 ft
- Room-cool setpoint range
- 64–86°F
- Spot-cool setpoint range
- 32–86°F
- Manufacturer sound level
- 75 dBA
- Mobility
- Heavy-duty twin-wheel casters