- Cooling capacity at 95°F / 60% RH
- 13,850 BTU/h; nominal 1.1 ton
- Nominal heating capacity
- 17,010 BTU/h; nominal 1.5 ton
- Electrical supply
- 115 V / single phase / 60 Hz
- Dimensions, width × depth × height
- 16 × 36 × 42 in
- Unit weight
- 221 lb
- Shipping weight
- 271 lb
- Cooling operating range at 50% RH
- 60–110°F
- Heating operating range at 50% RH
- 40–80°F
- Compressor
- Hermetic rotary
- Refrigerant
- R-454B
- Evaporator airflow
- 460 CFM
- Condenser airflow
- 700 CFM
- Fans
- Direct-drive centrifugal
- Condenser configuration
- Balanced inlet and outlet airflow
- Optional supply chute kit
- 2 chutes; 5 in diameter × 16 in length
- Optional condenser duct kit
- 2 ducts; 12 in diameter × 8 ft length
- Maximum condenser duct length
- 25 ft
- Current, heating / cooling
- 14.3 A / 14.1 A
- Power consumption
- 1.48 kW
- Maximum circuit breaker
- 20 A
- Recommended breaker
- 15 A
- Minimum circuit ampacity
- 17.65 A
- Minimum / maximum voltage
- 105–125 V
- Power cord
- 14 AWG / 6 ft
- Plug
- NEMA 5-15
- Optional ceiling kit CK-12 weight
- 38 lb
- Shipping weight including ceiling kit
- 309 lb
- Controls
- Digital thermostat
- Condensate management
- Internal high-lift pump with overflow protection
- Freeze protection
- Hot-gas bypass
- High-pressure switch
- Manual reset
- Low-pressure switch
- Automatic
- Power recovery
- Automatic restart
- Compressor short-cycle protection
- Included