Electric Heaters

Vactagon 150-kW Industrial Electric Heater — 460 V

The Vactagon 150-kW electric duct heater supplies 512,000 BTU/h with 6,000–8,000 CFM of blower airflow. Its industrial package combines a 10-hp variable-frequency-drive blower, staged heat controls and 20-inch inlet and outlet duct connections. A NEMA 4 control enclosure, filtered intake, steel lifting cage and fork pockets support industrial and shipyard heating setups. This profile covers the manufacturer’s 460-volt, three-phase configuration.

Specs & manuals ↓
Back to HVAC

Estimated equipment rental only. Delivery, taxes and applicable fees quoted separately. Final pricing confirmed with dispatch.

Specifications

Equipment

Manufacturer
Vactagon
Model
150kW Portable Heater with Blower — 460 V

Equipment specifications

Electric heat rating
150 kW
Published heat output
512,000 BTU/h
Airflow range
6,000–8,000 CFM
Electrical configuration
460 V, three-phase, 60 Hz
Published current
198 A
Heat stages
4
Heat output by stage
128,000 / 256,000 / 384,000 / 512,000 BTU/h
Blower motor
10 hp
Blower control
Variable-frequency drive; automatic multiple-speed settings
Weight
1,400 lb
Overall length
71 in
Overall width
49 in
Overall height
54 in
Inlet duct connection
One 20-in QF connection, clamp and hose adapter
Outlet duct connection
One 20-in QF connection, clamp and hose adapter
Electrical enclosure
NEMA 4
Electrical connections
E-1016 series cam-lock panel connections
Controls voltage
24 V
Disconnect
Disconnect switch
Heating elements
Finned tubular elements
Intake filter size
22 × 22 × 2 in
Intake filter rating
MERV 9
Airflow monitoring
Airflow switch with LED indicator
Thermal shutdown setting
250°F
Compartment insulation
1-in foil-faced insulation
Base and handling
Carbon-steel base, fork pockets and lifting cage
Stacking
Stackable cage
Finish
Epoxy primer and polyurethane topcoat

Equipment Details

Capabilities & Features

  • Industrial ducted heat
  • Staged electric heating
  • VFD blower
  • NEMA 4 enclosure
  • 20-inch duct connections
  • Filtered intake
  • Stackable lifting cage
  • Fork pockets

Available Options

  • 575 V, three-phase, 160 A factory variant
  • Stainless-steel enclosure or construction
  • Prewired power cable
  • Remote thermostat probe and display
  • Remote 2–10 VDC or 4–20 mA thermostat interface
  • Alternative slip-on duct connections and hoses