- Manufacturer / family
- YORK Latitude YCAV
- Model size / efficiency configurations
- YCAV0457; S standard efficiency or P optimized IPLV
- Rental equipment class
- 440 tons
- Reference configuration
- Style A, 60 Hz; S / P data shared unless identified separately
- Refrigerant
- R-134a
- Independent refrigerant circuits
- 4
- Compressors
- 4 direct-drive semi-hermetic rotary twin-screw compressors
- Capacity control
- Variable-speed drive; dedicated inverter per compressor
- Four-compressor family turndown
- Down to 5% of chiller capacity (manufacturer family specification)
- Chilled-water flow range
- 350–1,250 GPM
- Standard leaving-water temperature range
- 40–60°F
- Air-on-condenser operating range
- 0–125°F
- Evaporator type
- Direct expansion
- Evaporator water volume
- 266 gal
- Maximum standard water-side pressure
- 150 PSIG
- Maximum refrigerant-side evaporator pressure
- 235 PSIG
- Chilled-water inlet / outlet
- 10 in / 10 in
- Condenser construction
- Fin / tube with integral subcooler
- Total condenser coil face area
- 616 sq ft
- Condenser coil rows / fin spacing
- 3 rows / 17 fins per in
- Condenser fans by circuit, 1 / 2 / 3 / 4
- 6 / 5 / 5 / 5 (21 total)
- Fan diameter
- 35.4 in
- Low-noise fan speed
- 1,140 rpm (low-noise fan arrangement)
- Ultra-quiet fan speed
- 838 rpm (ultra-quiet fan arrangement)
- Total chiller airflow, manufacturer physical table
- 273,000 CFM
- Oil charge by circuit
- 5 / 5 / 5 / 5 gal
- Refrigerant charge by circuit
- 230 / 185 / 185 / 185 lb, R-134a
- VSD cooling-loop charge
- 9.3 gal at 43% glycol concentration
- Standard electrical arrangement, four-compressor family
- Multi-point power connections; factory-wired control transformer
- Control transformer secondary
- 115 V / single-phase
- Power / control enclosure
- NEMA 3R (IP55), powder-painted steel
- Manufacturer drawing length
- 572 7/8 in
- Manufacturer drawing height
- 95 9/16 in
- Manufacturer drawing base width
- 88 1/4 in
- Factory nominal capacity table
- 439.3 tons at 95°F condenser air, 44°F leaving water and 2.4 GPM per ton
- S / P full-load EER, nominal table
- 9.8 (includes compressor, fan and 0.8 kW control-panel power)
- S configuration standard IPLV, nominal table
- 12.8
- P configuration optimized IPLV, nominal table
- 14.8