Diesel Generators

AIRMAN SDG45S-8E2 — 36 kW Prime Diesel Generator

The SDG45S-8E2 supplies 36 kW of three-phase prime power for temporary industrial loads. Its sound-attenuated steel enclosure combines a digital DSE controller, selectable output voltages and 80.5 gal fuel storage. External fuel connections, service access and 110% fluid containment support extended site operation; unit and trailer dimensions are listed separately.

Specs & manuals ↓
Back to Power Solutions

Estimated equipment rental only. Delivery, taxes and applicable fees quoted separately. Final pricing confirmed with dispatch.

Specifications

Equipment

Manufacturer
AIRMAN
Model
SDG45S-8E2

Equipment specifications

Three-phase prime output
36 kW / 45 kVA
Three-phase standby output
38.8 kW / 48.5 kVA
Frequency
60 Hz
Fuel
Ultra-low-sulfur diesel
Engine
ISUZU 4LE2X
Fuel tank capacity
80.5 gal
Three-phase voltage selection
208 /220 /240 /416 /440 /480 V
Current at 208 V, three phase
119 A
Current at 240 V, three phase
108 A
Current at 480 V, three phase
54 A
Three-phase power factor
0.8
Alternator
AIRMAN WYE winding
Excitation
Brushless with AVR
Number of poles
4
Voltage regulation
±0.5%
Frequency regulation, steady state
±0.25% of overall mean
Controller
DSE 7310 MKII
Engine speed
1,800 rpm
Engine cylinders
4
Engine displacement
133 in³
Engine rated output at 1,800 rpm
57.7 BHP
SAE gross output at 1,800 rpm
65.7 BHP
Governor
Electronic
Engine emissions
Tier 4 Final
Aftertreatment
Diesel oxidation catalyst (DOC)
Fuel consumption at full /75% /50% load
2.8 / 2.1 / 1.5 gal/h
Runtime at full load
28.75 h
Engine lubricating-oil capacity
3.1 gal
Coolant capacity
2.5 gal
Sound at 23 ft, no-load /full-load
57 / 61 dB(A)
Unit dry weight
2,954 lb
Unit operating weight
3,337 lb
Trailer weight
1,182 lb
Operating weight with trailer
4,519 lb
Unit dimensions (L × W × H)
74.8 × 38.2 × 61.4 in
Trailer dimensions with generator (L × W × H)
144 × 70 × 73 in
Fluid containment
110%
Enclosure
Powder-coated 16-gauge steel
Door hinges and service hardware
Stainless steel
Fuel connection
External tank connection with selector valve
Cooling
Liquid/air fin-and-tube radiator; 50/50 coolant mix
240 V single-phase prime output
26 kW
240 V single-phase standby output
28 kW
Single-phase selectable voltages
120 /127 /139 /240 /254 /277 V

Equipment Details

Capabilities & Features

  • DSE digital controls and electrical protection
  • Selectable three-phase output voltages
  • 110% fluid containment and external fuel connection
  • Sound-attenuated enclosure with lockable access

Available Options

  • SmartLoad automatic load optimization
  • Cam-lock output connections
  • Cold-weather equipment
Become Operational

Need this on a mission profile?