Direct Fired Heaters

L.B. White Premier 350 DF 2.0 (CS350) — Ductable Dual-Fuel Heater

The L.B. White Premier 350 DF 2.0 (CS350) is a ductable, enclosed-flame direct-fired heater with 350,000 BTU/h input on propane or natural gas. It supports temporary construction heating and documented tent-heating applications, with flexible duct and diffuser arrangements for distributing warm air. The 120-volt unit has a 1-HP blower drive, heat and ventilation controls, and a thermostat. Its LINK Capable configuration can accept the factory telematics installation kit. The manufacturer lists a 256-pound weight and dimensions of 48 by 22.25 by 32.75 inches.

Specs & manuals ↓
Back to HVAC

Estimated equipment rental only. Delivery, taxes and applicable fees quoted separately. Final pricing confirmed with dispatch.

Specifications

Equipment

Manufacturer
L.B. White
Model
Premier 350 DF 2.0 (CS350)

Equipment specifications

Maximum heat input
350,000 BTU/h / 102.6 kW
Fuel
Propane or natural gas; dual-fuel configuration
Heater type
Ductable direct gas-fired forced-air heater
Electrical supply
120 V, 60 Hz, single-phase
Starting / continuous current
25.0 / 11.0 A
Equipment weight
256 lb
Length × width × height
48 × 22.25 × 32.75 in
Gas inlet pressure range
11.0–13.5 in water column
Burner manifold pressure
8.0 in water column
Propane consumption
16.2 lb/h
Natural-gas consumption
350 cu ft/h
Motor
1 HP; ball-bearing; 1,725 rpm
Blower speed
915 rpm
Minimum operating ambient temperature
−20°F
Maximum flex-duct arrangement
Three 12-ft × 18-in flex ducts; without end diffuser
Flex duct with end diffuser
One 12-ft × 18-in duct
Flex ducts with inflatable distribution duct
Two flex ducts maximum
Controls
Heat / off / ventilation selector and thermostat
Telematics provision
LINK Capable; installation kit available
Combustible clearance, top / sides / back
1 / 1 / 1 ft
Combustible clearance, blower outlet
6 ft
Application approval
Construction heating and U.S./Canadian tent heating with temporary human occupancy
Manufacturer test laboratory
OMNI Test Laboratories; report0545GH007S

Equipment Details

Capabilities & Features

  • Enclosed-flame ductable heat
  • Dual-fuel gas selector
  • Heat and ventilation modes
  • Thermostat control
  • Wheels and lifting handles
  • LINK Capable wiring provision

Available Options

  • Flex ducts and adapters
  • End diffuser
  • Inflatable air-distribution duct
  • LINK Capable power box and telematics kit
Become Operational

Need this on a mission profile?

We scope, qualify and deploy the right fleet — managed end to end, tracked on GC.